Terms Used.
UV Flame Detectors. These detect ultraviolet radiation from a flame.
‘Inference’ Flame Detection. This is a software program to detect flame
from PT Exit temperature rise.
1. IGNITION.
For ignition of the four pilot flames two three things are needed.
a.
Air supplied by the turbine
gas generator.
b.
A correct flow of fuel into
the igniter blocks.
c.
A good spark to ignite the
igniter gas.
2.0 Air.
This is not adjustable on an electric motor start. The control system
will not switch on the igniters until a gas generator speed of greater than
1800 rpm has been reached and the engine has had enough air through to be
purged of any fuel gas. For gas motor starting or hydraulic, at least 1800 rpm
is necessary by the time igniters are switched on (40 seconds norbit) or to
start the core purge timer. If the starter reaches more than 2800 rpm before
main fuel is on the governor can start ramping the throttle open causing
stalling and high temperature shut down.
Pilot fuel will usually light OK.
3.0 Igniter fuel.
3.1
Propane has been found to be the most reliable pilot fuel if good
quality propane is available, it also has a standard set up. An alternative is
using main gas fuel but this will need adjustments to be made to the igniter
fuel system to increase flow. Some natural gas fuel is low in UV output so
cannot easily be detected by UV detectors. Low calorific value gas fuel makes
it difficult to detect pilot flames by temperature rise.
Logic modifications to bring main fuel on four seconds after pilot fuel
help the Ultra Violet or inference flame detection systems because main flames
will be easier to detect than pilot flames. In this case even if one combustion
chamber is not lit sufficient heat from the others will cause flame to be
detected but the will shut down on deviation.
3.2
Containers of propane need to be large enough and full enough to
generate sufficient gas at the necessary
pressure during the light up period and for rapid restarts. Propane bottles
will need to be joined in parallel when small ones are used or where they are
located a distance away from the turbine or where there are additional pressure
drops in the system.
3.3
To provide the correct flow of
igniter gas is done either by a PCV (Pressure Control Valve ) or an orifice
normally located after the filter (See diagram 1) in the fuel valve module.
In the case of diagram 1, as well as a PCV in the fuel module, extra
PCV’s are fitted on the bottles and an orifice is fitted in the main gas supply
line. In this case the on skid PCV was wound full open and the pressure was
regulated by the PCV’s on the propane bottles or by the orifice in the main gas
supply line.
3.4
Many sites will need the propane
bottles to be heated to maintain sufficient pressure. Others in cold climates
where the turbine is outside will need the pipe to the turbine trace heated and
lagged to prevent the propane condensing.
3.5
Tests have shown that for
optimum recognition of a propane pilot flame by UV detectors, a pressure of
45-48 psig before the four 1/16th inch orifices is required. Lower
pressure can lead to late recognition on one pilot burner and higher pressures
can lead to an unstable flame and the UV detectors losing sight of it. When
inference detection is used, higher pressures will give more temperature rise
and faster detection.
If a gauge is fitted it can be seen quickly whether the propane supply
is sufficient and corrected as necessary.
NOTE Turbines can vary in the optimum pressures for light up. The
object is to set pressures so that all four flames light quickly and stay
stable.
3.6
Pressures for optimum main gas pilot fuel ignition will be higher than
for propane. Tests on one onshore supply showed that approximately 60 psig
before the 1.16th orifices was needed for UV detection. Other sites may need higher pressures.
High pilot fuel flow has been found to cause the gas generator to
accelerate above 28%, 2800 rpm and ramp the throttle open before main fuel is
switched on. This can lead to high temperatures or stall due to high heat
input. (Affects turbines more when gas start and 4 flames detected needed for
main fuel).
4.0 Spark igniters.
4.1
The method of lighting the pilot fuel is by a spark plug. The spark
plugs are connected to units(polarity sensitive) that input nominal 24 volts DC
and output high voltage pulses sufficient to generate sparking at the plug.
Where there are long distances between the 24 volt dc supply and the
igniter units, voltage drop on the supply cables can a problem leading to weak
or intermittent sparks. Either an extra battery cell to increase the supply
voltage or greater cross section cables can cure the problem.
4.2
Gaps of 0.025 inch between the outer electrodes and the inner of the
spark plug are recommended and should produce the optimum spark .
4.3
It is possible for the spark units can fail or produce a weak or
intermittent spark so reducing start reliability and for the flexible leads
from the igniter unit to be damaged.
Replacement of these parts are the cure.
4.4
TB4000 and TB5000 igniter leads are not interchangeable, retrofit units
have had problems when fitting TB4000 leads directly to the igniter unit.
5.0 Ignition Fault Finding.
5.1
Find which pilot flame(s) are not being lit.
Use the control system to indicate which
combustion chamber either did not
light or lit late. Late ignition indication
on the control system may mean that
the pilot flame did not light or is receiving
insufficient gas.
Observing for presence of flame through the
sight glasses on the combustion
chamber can be useful.
5.2
Check that there is plenty of pilot fuel.
Propane bottles may be low in
pressure, if so fit full ones.
5.3
Check that the 1/16 th orifices are clear on
the suspect combustion chamber.
Blow out with air.
5.4
Check that the non return valves after the
orifices are working. Replace if
necessary.
5.5
Check that the correct pressure is being
achieved before the 1/16 th orifices.
If pressure incorrect investigate why.
5.6
Check
for leaks. Repair as necessary.
5.7
Check the spark plug, check
gaps or for damage and replace if necessary.
5.8
Check for sparks. Replace
spark plug or spark unit or leads.
5.9
Check for 24 volt supply to
the turbine skid with igniters switched on.
If there is a large volt
drop with the igniters turned on the cable from the supply will need increasing
in size, or the voltage increased to compensate.
5.10
Check for condensing pilot
fuel. Cold weather can cause this. Pipe from the propane bottles should be
heated and lagged.
5.11
Check for correct operation
of the solenoid valve and blockages in the propane line. Replace or repair
components as applicable.
6.0 Main Fuel ON.
6.1 When electric 4
to 2 pole motors are used the main fuel should cause the change from 4 to 2
pole by reducing the current through the motor. An undercurrent relay should be
set so that the motor cannot change to 2 pole until main fuel is on and lit.
Changing to 2 pole without main fuel on and lit can burn out motors and
starters because the motor has insufficient torque to accelerate the gas
generator and will stay on starting current which is at least 6 times full load
current.
6.2 Once the pilot
fuel is lighting up reliably it may be that the turbine trips on deviation. A
likely cause is dirty burners or low fuel flow at the point of main fuel on. If flow is very low one
combustion chamber may get less than the others and as the turbine accelerates
and deviation limits close a deviation shutdown can happen. A simple solution
is to increase the light up flow of fuel. Indications of this problem is that
it is more likely when the turbine is cold. Bad deviation is an indication that
burners are not clean and will also show as poor spread.
6.3 Stalling.
This is where the
temperature rises without the gas generator accelerating.
Stalling can happen at main
fuel on but the starter motor will continue to accelerate the gas generator.
The stall is likely to sound unusual.
If happening at light up the
light up fuel demand can be reduced although this can lead to deviation shut
down.
If the stall happens after
light up there are two fuel rates that can be reduced to reduce the chance of
stall. This may be necessary in the case of a turbine that uses solids cleaning
when running just to achieve a start. In such cases the turbine is more likely
to start cold.
A cold wash on a dirty
engine can increase air flow and reduce chances of a stall.
7.0 STARTER OFF.
7.1 The starter dog
is disconnected at a CT speed of 4800 rpm and the starter motor switched off.
Also the fuel input changes to a slower ramp rate. A STALL can then be detected
with slow or no acceleration of the gas generator and increase of engine
exhaust temperatures. This can be due to over fuel which is due to a dirty or
worn gas generator supplying insufficient air.
If fuel input is correct (ramp rate 1) and
turbine is in good condition the amount of fuel at starter off should be
sufficient to maintain the CT speed and continue acceleration smoothly but at a
slower rate.
7.2 IGV’s in open
position. It should not be possible for the turbine to start with IGV’s open,
check micro switch operation. IGV change over should be at above 9000 rpm CT
speed.
7.3 Interstage BOV’s closed. This can cause
stalling if stuck shut. They should be nearly closed at generator no load or
very low load and close tight with more than 200-300 kW. On some turbines the
interstage BOV’s close at no load. The purpose of the interstage BOV’s is to
prevent surging by dumping excess air from the middle stages of the CT which
cannot be coped with by the hp stages during the start. Also when load is put
on the turbine from zero if surging takes place, later closing BOV’s can help
prevent it.
7.4 Electric centre
casing BOV’s open or leaking. If these leak or fail to close the result is
likely to be high PT exit temperatures during this period of the start or
during no load running.
Causes could be the diaphragm damaged, the valve seat damaged, blocked
orifices, pipe leaks or leaking ASCO solenoid valves.
Note: 4 off ASCO solenoid valves
are fitted to TB5000 or up-rated TB4000 turbines.
8.0 Poor governing at
no load.
8.1 More fuel than
demanded. At no load the fuel should be in the region of 14-15 degrees for electronic
actuator (approx. 3800kw for STAR systems). If the fuel is at 11 degrees or
sitting on the blow out limits for long periods at no load then the fuel
regulation is incorrect and it will be difficult to keep speed low. The control
system will not allow less than the above fuel demands to prevent the flames
blowing out. High regulated gas pressure for electronic actuator systems can
cause this problem.
For STAR actuator
systems the normal no load heat demand must be higher than the blow out flow
setting.
If more is being put into the turbine than asked for the speed can rise
and the centre casing blow of valves will open. Usually set to open on 4% above
demand speed.
Generators would have difficulty synchronising with others with this
problem.
ADJUSTMENTS TO THE CONTROL
SYSTEM SHOULD ONLY BE DONE BY COMPETENT
PERSONNEL.
Hi Emad, I am Roberto Mendez from Mexico.
ReplyDeleteDo you know where can be carried out performance test for Ruston Turbines TB-5000/5400 after they were overhauled?
The information you posted is very intresting.
ReplyDeleteRegards
Hio emad
ReplyDeleteIf the machine trips on accelerattion low GG 4800 rpm, what will be the causes
Looking for TB5000 ignition parts? Contact Task-Pro (Aberdeen). Coils, igniter leads & plugs all kept in stock
ReplyDeleteYour information is very useful! I operate the TВ-5000. I will be glad to see new articles and cooperation.
ReplyDelete